- Checking 16 zones of fireguard alarm (FGA).
- Support up to 4 partitions with independent setting/removal of guard mode.
- Compatible operation with devices “Cupol-16”, “Cupol-TRS”, “Cupol-GSM”, “Cupol-4MP”.
- Built-in Touch Memory controller.
- Up to 16 control panels can be united in local network
- Programming with help of PS-24 programmer.
Need a consult?
Our experts will answer any technical questionThe control panel “Cupol-16T” is intended to check 16 zones of fireguard alarm (FGA). The operation is performed in autonomous mode with supplying sound and light signals and simultaneous transmitting the notifications over the RS485 wire line.
The following communication channels combination can be used to transmit information to CSC:
- Radiochannel.
Information from the control panel is transmitted over the RS485 wire line to “Cupol-TRS”, “Cupol-16” or “Cupol-4MP”, which is a concentrator collecting, processing and transmitting the notifications over the radiochannel to CSC. - GSM channel (GPRS).
Information from the control panel is transmitted over the wire line RS485 to “Cupol-GSM”, which collects, processes and transmits notifications over the GSM (GPRS) channel to CSC. - RS485 wire line.
Information from the control panel is transmitted over the RS485 wire line directly to PC with appropriate set software through matching adapter “USB-485”.
To increase reliability of notification delivery, simultaneous using the radio and GSM channel are possible.
The control panel realizes the notification reception by means of measuring and checking the resistance value of FGA zone. As sensors inserted in FGA zone, guard and fire sensors of electro-contact type with relay output and sensors with feeding over the cable can be used.
The following information is transmitted over communication channels:
- user code (up to 64 users including codes “quiet alarm”);
- status of zones (current status of zone, type, pass/fail etc.);
- violating zones described as zones with delay;
- “alarm” button calling;
- fire alarm on the object;
- power supply mode (main power supply, reserve accumulator discharge level, work condition of connected UPS and so on);
- equipment unauthorized opening event;
- user information addressed to CSC dispatcher;
- current state information about the object (guard/on duty mode, violation zone events while interval guarding, excluded zones and so on).
Support of the following zone types:
- fast zone (transmitting the alarm notifications performs immediately after zone violating);
- zone with delay (transmitting the alarm notifications performs in specified time interval after zone violating);
- inner zone (transmitting the alarm notifications performs immediately after zone violating or in specified time interval if zones with delay were violated before);
- round-clock zone (guard round-clock zone, independent of the whole object guarding, immediate transmitting the alarm notification);
- fire zone (priority transmitting of fire alarm notification).
The control panel allows to:
- Check the status of zones;
- Make the calibration of inputs;
- Set and delete codes of user electronic keys;
- Make setting/removing the guarding mode;
- Program device parameters.
Programming of the control panel is possible after connection with the computer under appropriate software control.
Feeding the control panel is performed over the RS485 line from the power supply “Cupol-TRS” or outer back-UPS “Cupol-IBP”.
The equipment operates in the round-clock mode, the operating temperature is +5 °C to +40 °C, the relative humidity is up to 93% (at 40 °C).
Specifications | |
Number of FGA zones “Cupol-16T” | 16 |
Number of supported partitions, max | 4 |
Number of notifications, over | 200 |
Total resistance of zone with terminating resistor, kOhm | 0.5…5 |
Time reaction of control panel after any zone violating (program specified with step 50 ms separately for each zone) | 50 ms…60 s |
Alarm notification time delay after zone violating (program specified with step 1 s separately for each zone), s | 1…255 |
Zone measuring current, mA, or less | 1 |
Electronic key types (w/o auxiliary equipment) | DALLAS DS199X |
Number of control outputs | 5 |
…from them switching relay contact | 1 |
…from them open collector type | 4 |
Number of programmed functions for each output | 49 |
Communication interface | RS-285, RS-485 |
Max number of simultaneous used frequency channels | 3 |
Information transmitting period over the radiochannel, min (or in case of object event) | 1…255 |
Operating voltage, V | 10.5…14.4 |
Dimension, mm, approx | 160x130x45 |
Weight, kg, approx | 0.4 |