- Checking 8 zones of fire-guard alarm (FGA).
- One or multi-frequency operation capability in range 146-174MHz.
- Antenna-feeder equipment efficiency continuous checking.
- Built-in controller of Touch Memory.
- Device programming with help of PS-24 programmer.
Need a consult?
Our experts will answer any technical questionControl panel “Cupol-4” is intended for checking 8 zones of the fire-guard alarm (FGA). The operation is performed in autonomous mode with supplying sound and light signals and simultaneous transmitting the notifications over the radiochannel to the centralized supervisor console (CSC).
Main application is centralized or autonomous guarding of the objects.
The control panel realizes the notification reception by means of measuring and checking the resistance value of FGA zone. As sensors inserted in FGA zone, guard and fire sensors of electro-contact type with relay output and sensors with feeding over the cable can be used
Information transmitted over the radiochannel:
- current time on the object (month, day, hour, minutes, seconds);
- user code (up to 32 users including codes “quiet alarm”);
- status of zones (current status of zone, type, pass/fail etc..);
- violating zones described as zones with delay;
- “alarm” button calling;
- fire alarm on the object;
- power supply mode (main power supply, reserve accumulator discharge level, work condition of connected UPS and so on);
- antenna-feeder equipment and transmitter work condition;
- equipment unauthorized opening event;
- user information addressed to CSC dispatcher;
- current state information about the object (guard/on duty mode, violation zone events while interval guarding, excluded zones and so on).
While transmitting over the air, the special coding and information integrity checking is performed that allows to provide high interference protection and large operation radius of the system, protecting from unauthorized access to the radiochannel.
The devise provides zone status checking by means of measuring its resistance value. While mounting on the object, devices are automatically calibrated under the appropriated zone resistance and terminating resistors. Total zone resistance and terminating resistor should be in range 0, 5…5 kOhm.
The control panel has an event book, which stores up to 500 last events caused with the object.
The control panel allows to:
- Check the status of zones;
- Make the calibration of inputs;
- Set and delete codes of user electronic keys;
- Check the antenna-feeder section;
- Make setting/removing the guarding mode;
- Program device parameters.
Programming of the control panel is possible after connection with the computer under appropriate software control.
The control panel is transmitted the information over three channels: a telemetric channel, duplicating channel and alarm channel. The telemetric channel is a main guard channel. It transmits alarm notifications, events and telemetric guard information. The duplicating channel performs transmitting alarm notifications and events and does not transmit telemetric information.
Support of the following zone types:
- fast zone (transmitting the alarm notifications performs immediately after zone violating);
- zone with delay (transmitting the alarm notifications performs in specified time interval after zone violating);
- inner zone (transmitting the alarm notifications performs immediately after zone violating or in specified time interval if zones with delay were violated before);
- round-clock zone (guard round-clock zone, independent of the whole object guarding, immediate transmitting the alarm notification);
- fire zone (priority transmitting of fire alarm notification).
The equipment operates in the round-clock mode, the operating temperature is +5 °C to +40 °C, the relative humidity is up to 93% (at 40 °C).
Specifications | |
Number of FGA zones “Cupol-4” | 8 |
Number of notifications, over | 200 |
Total resistance of zone with terminating resistor, kOhm | 0,5…5 |
Reaction time of control panel after any zone violating (program specified with step 50 ms separately for each zone) | 50 ms…60 s |
Alarm notification time delay after zone violating (program specified with step 1 s separately for each zone), s | 1…255 |
Zone measuring current, mA, or less | 1 |
Supported electronic key types (w/o auxiliary equipment) | DALLAS DS199X |
Number of control outputs | 5 |
…from them switching relay contact | 1 |
…from them open collector type | 4 |
Number of programmed functions for each output | 49 |
Control panel output power at 50 Ohm load, W: | |
Power level 1 | 5±2 |
Power level 2 | 2±1 |
Operating frequency range, MHz | 146…174 |
Signal modulation type | 16K0F2D |
Frequency step resolution, kHz | 25 |
Operative offset frequency range, MHz | ±3 from the central frequency |
Max deviation of control panel transmitter frequency, kHz | 5 |
Transmitter emission frequency bandwidth at minus 30 dB level, kHz, or less | 16.8 |
Transmitter emission level in adjacent channel, uW, or less | 2.5 |
Transmitter spurious level, uW, or less | 2.5 |
Transmitter frequency deviation from nominal value, or less | 10*10-6 |
Antenna connector | BNC |
Max number of simultaneous used frequency channels | 3 |
Support of keyboards | RS-232 |
Information transmitting period over the radiochannel, min (or in case of object event) | 1…255 |
Information transmitting time over the radiochannel, s, or less | 0.6 |
Operating voltage, V | 10.5…14.4 |
Current consumption from the source +12 V (while operating voltage +12 V), A, or less | 2.2 |
Current consumption in case of transmitting absence, mA, or less | 200 |
Dimension, mm, approx | 160x130x45 |
Weight, kg, approx | 0.4 |